Precise conductivity measurement with minimal energy consumption

How a battery-powered measuring device reliably measures the electrical conductivity of heating water across a 100-fold range of values – using a simple sample-and-hold method instead of complex impedance measurement.

Process water must comply with the technical guidelines issued by manufacturers and professional associations in terms of its chemical and physical properties. In Switzerland, this is set out in the SWKI BT102-01 guideline ‘Water Quality for Building Services Systems’. For example, heating water must have a specific conductivity of less than 200 µS/cm, whilst make-up and top-up water must be below 100 µS/cm. Dissolved minerals and corrosion products cause conductivity to rise. If it exceeds the limit value specified in the standard, the water must be treated using an ion exchanger to prevent limescale and corrosion damage to the system. For a portable, battery-powered measuring device that records this value, together with flow rate and temperature, directly within the system or at a mobile filling station, logs the data and transmits it via Bluetooth, the question arises: how can conductivity be measured accurately enough across several orders of magnitude (10 µS/cm to 1000 µS/cm) without requiring the methodology of a full-scale laboratory instrument?

From the requirement to the measurement method

The challenge lies in achieving precise conductivity measurements with minimal energy consumption across a wide measurement range, whilst at the same time meeting the requirements of a compact, battery-powered device. Below, we demonstrate how these requirements can be met using a deliberately simple measurement approach, and explain why no complex impedance measurement is necessary.

A view into a boiler room with lots of pipes

The conductivity of system water cannot simply be measured using direct current: an electrochemical double layer forms at the interface between the electrode and the liquid, which acts like a capacitor and increasingly polarises the electrode when direct current is applied, causing the measurement signal to drift over time. The cell must therefore be excited using alternating current. Its impedance consists of an ohmic and a capacitive component. A high-end solution would measure this complex impedance in full via a frequency sweep, in terms of magnitude and phase – precisely, but with a noticeable drain on the microcontroller’s power and computational resources for continuous sinusoidal excitation, synchronous demodulation and spectral analysis.

A pragmatic approach to conductivity measurement

Graphical representation of the measurement principle

As the measuring cell is permanently installed in the device and the required measuring range is known, the electronics themselves do not need to be able to measure an unknown cell across an entire frequency spectrum. The optimum frequency can be determined once in the laboratory and stored permanently in the device. Instead, during operation, the cell is excited by a bipolar square-wave signal, generated by a simple digital-to-analogue converter (DAC) with downstream analogue switches, rather than a sine wave generator. The voltage drop across the cell is conditioned by an instrument amplifier to a signal level suitable for further processing and sampled by two parallel sample-and-hold stages at precisely defined time points within each half-wave. If these sampling times are set so that the capacitive transient has already decayed, the difference between the two held voltage values directly provides the ohmic component, which is proportional to the conductance, without the need for any phase measurement or frequency sweep. A short excitation sequence per measurement is sufficient. Although the excitation itself is bipolar, the circuit operates on a unipolar supply voltage. This reduces circuit complexity and is ideally suited to low-power, battery-operated measuring instruments.

Optimisation of frequency and sampling times

In order to determine the optimum excitation frequency and the appropriate sampling times for our own two-electrode cell, which is integrated into the flow channel, it was first characterised using a network analyser. The same pattern is observed across a range of conductivities: From a few hundred hertz onwards, the curve flattens out into a plateau where the magnitude corresponds to the desired ohmic resistance and the phase is close to 0°. Only at very high frequencies and low conductivities does a capacitive influence become noticeable again. From this plateau, the excitation frequency and sampling times could be determined in such a way that the effects of polarisation and capacitance remain minimal.
solutions-precise-conductivity-measurement_impedance-magnitude.svg

Integration into the flow channel

Side view of the flow channel

In addition to conductivity, the device also measures the flow rate and temperature of the system water via a flow sensor integrated into the same channel. The temperature is not merely an additional measured value: as the conductivity of water increases by around two per cent per Kelvin, the microcontroller converts the measured raw value to the reference temperature of 25 °C. The two electrodes are pressed in tangentially to the flow channel. This ensures that both their mutual distance and the wetted surface area remain constant, which improves reproducibility in mass production. This prevents oblique insertion, tolerance issues caused by varying insertion depths or part lengths, and subsequent mechanical deformation of the electrodes. At the same time, the arrangement integrated into the flow channel prevents foreign particles or air bubbles from accumulating on the electrodes. The additional temperature sensor is positioned close to the electrodes, thereby enabling precise temperature compensation without affecting the temperature measurement. Furthermore, the tangential arrangement of the electrodes has only a minimal effect on the water flow. Backflow is prevented, ensuring that the subsequent flow rate measurement is not distorted.

Meaningful data for plant operation

Taken together, conductivity and the volume of water that has flowed through provide a clear indication of whether the conductivity is below the threshold and how much longer any ion exchanger will continue to supply system water of the required quality before it needs to be replaced. All measured values are logged and are available via Bluetooth for mobile analysis, as well as optionally via Modbus for integration into the building management system.

The result is an accuracy in the low single-digit percentage range, which is entirely sufficient for the application, whilst requiring only a fraction of the power and computational effort that a full impedance measurement would entail. This is an example of how the most pragmatic solution is often not the most technically complex, but rather the one that best suits the product’s constraints.
A profile of the two authors of the academic article, Ronald Reichmuth and Adrian Braun

“In this development, the focus was not on the most technically complex solution, but on the one offering the greatest practical benefit. The result shows that precision, robustness and energy efficiency can be successfully combined.”

Ronald Reichmuth, hardware and firmware developer, and Adrian Braun, mechanical development engineer at STEINEL Solutions AG

Author: Ronald Reichmuth, hardware and firmware developer & Adrian Braun, mechanical development engineer